Diese Seiten sind technisch und auf Englisch. Sie sammeln, was die Mitwirkenden von OpenAmpere über die Geräte herausgefunden haben, jeweils mit Quelle und wie sicher die Angabe ist. Sie zeigen den neuesten Stand der Entwicklung, der manchmal schon über deine installierte Version hinausgeht. Es sind keine offiziellen Angaben der Hersteller. Für die Einrichtung brauchst du sie nicht, die App erklärt dir alles Nötige.

FoxESS H3, register map of newer firmware

Not official manufacturer information: compiled by the OpenAmpere contributors, possibly incomplete or wrong. Changing inverter settings can affect warranty and grid connection rules. No affiliation with FoxESS or EKD, not legal advice. See Device knowledge.

Applies to: FoxESS H3 with newer firmware, H3 Smart, H3 Pro (probably the E3) · Sold as: see h3.md · OpenAmpere: driver foxess, register map foxess_h3_new · Support: display and control · Confirmed on a real device: partly (reading and control on an H3 with newer firmware; H3 Smart and H3 Pro not)

Family facts (detection, connection limits, remote control behaviour, decisions on grid charging) are on h3.md; the older map is on h3-legacy-map.md.

Summary

Registers

Read in blocks (start + count): 37002+1, 37609+24, 38309+8, 38814+8, 38901+15, 39063+15, 39118+2, 39141+1, 39219+20, 39279+8, 39327+12, 39601+32. Addresses inside a block that are not listed below are read but not used. Model string 30000–30015: see h3.md. FC04 = input register, FC03 = holding register.

RegisterMeaningType, scale, signR/WStatusSource
30016–30031Serial number (on this map only)ASCII, 16 registersR (detected FC, then FC03, FC04)derivednathanmarlor/foxess_modbus; registers.py
36001–36003Firmware: master, slave, managerU16; shown as master/100, slave/100, manager in hexR (detected FC, then FC03, FC04)derivednathanmarlor/foxess_modbus; driver.py
37002BMS1 connected, 1 = yes; at 0 OpenAmpere drops SoC and battery temperaturesU16, 0/1R FC04 (optional block)confirmed (reads 1 with a connected battery)nathanmarlor/foxess_modbus; #19, #44
37609Battery voltageU16, ×0.1 VR FC04derivednathanmarlor/foxess_modbus
37610Battery currentI16, ×0.1 AR FC04derivednathanmarlor/foxess_modbus
37611"Battery temperature": temperature of the BMS electronics, not of the cellsI16, ×0.1 °CR FC04confirmed (meaning)nathanmarlor/foxess_modbus; #16, #41
37612State of chargeU16, %R FC04derivednathanmarlor/foxess_modbus
37617Highest cell temperatureI16, ×0.1 °CR FC04derivednathanmarlor/foxess_modbus
37618Lowest cell temperatureI16, ×0.1 °CR FC04derivednathanmarlor/foxess_modbus
37619 / 37620Highest / lowest cell voltagemVread in the block, not usedderivednathanmarlor/foxess_modbus; docs/registers.md
37624State of health (SoH)U16, %R FC04derivednathanmarlor/foxess_modbus
37632Remaining capacitynot stated in the sourcesread in the block, not usedderivednathanmarlor/foxess_modbus; docs/registers.md
37700BMS2 connectedflagnot readderivednathanmarlor/foxess_modbus; docs/registers.md
38309Second battery module (BMS2) temperatureI16, ×0.1 °CR FC04 (optional block)derivednathanmarlor/foxess_modbus
38315BMS2 highest cell temperatureI16, ×0.1 °CR FC04 (optional block)derivednathanmarlor/foxess_modbus
38316BMS2 lowest cell temperatureI16, ×0.1 °CR FC04 (optional block)derivednathanmarlor/foxess_modbus
38814–38815Grid power, totalI32, ×0.1 W, + = export (OpenAmpere negates it: + = import)R FC04derivednathanmarlor/foxess_modbus
38816–38821Grid power L1, L2, L3I32 each, ×0.1 Wread in the block, not usedderivednathanmarlor/foxess_modbus; docs/registers.md
38901Meter 2 (external PV) active, = 1flagR FC04 (optional block 38901+15)derived, confirmed (active on one EKD system with a second PV inverter)nathanmarlor/foxess_modbus; docs/registers.md; owner's diagnostics report in #635
38914–38915Meter 2 (external PV) power, + = generationI32, ×0.1 WR FC04, as the second PV inverter while 38901 = 1derived, sign confirmed on one device by the energy balance (#635)nathanmarlor/foxess_modbus; docs/registers.md; #635
39063Inverter state (status code)U16R FC04 (optional block)derivednathanmarlor/foxess_modbus
39065–39066Flags; bit 0 = off-grid (grid disconnected, backup operation)U32R FC04derived; bit seen set on a real device, once spuriously (#48, #50, #89)nathanmarlor/foxess_modbus; #89, #90
39067 / 39068 / 39069Alarm words 1, 2, 3U16 eachR FC04derivednathanmarlor/foxess_modbus
39070 / 39071PV1 voltage / currentI16, ×0.1 V / I16, ×0.01 AR FC04derivednathanmarlor/foxess_modbus
39072 / 39073PV2 voltage / currentI16, ×0.1 V / I16, ×0.01 AR FC04derivednathanmarlor/foxess_modbus
39074 / 39075PV3 voltage / currentI16, ×0.1 V / I16, ×0.01 AR FC04derivednathanmarlor/foxess_modbus
39076 / 39077PV4 voltage / currentI16, ×0.1 V / I16, ×0.01 AR FC04derivednathanmarlor/foxess_modbus
39118–39119PV power, total (documented as "PV total (E3)")I32, WR FC04 (optional block)derivednathanmarlor/foxess_modbus; docs/registers.md
39141Inverter temperatureI16, ×0.1 °CR FC04 (optional block)confirmed (scale checked against another reader on an H3)nathanmarlor/foxess_modbus; #11, #26
39219–39224House consumption L1, L2, L3I32 each, Wread in the block, not usedderivednathanmarlor/foxess_modbus; docs/registers.md
39225–39226House consumption, totalI32, WR FC04derivednathanmarlor/foxess_modbus
39237–39238Battery powerI32, W, + = dischargingR FC04derivednathanmarlor/foxess_modbus
39279 / 39281 / 39283 / 39285PV1, PV2, PV3, PV4 power (2 registers each)I32, WR FC04 (optional block)derivednathanmarlor/foxess_modbus
39327 / 39328 / 39329–39330MPPT1 voltage / current / powerI16, ×0.1 V / I16, ×0.01 A / I32, WR FC04 (optional block)derivednathanmarlor/foxess_modbus
39331 / 39332 / 39333–39334MPPT2 voltage / current / powerI16, ×0.1 V / I16, ×0.01 A / I32, WR FC04 (optional block)derivednathanmarlor/foxess_modbus
39335 / 39336 / 39337–39338MPPT3 voltage / current / powerI16, ×0.1 V / I16, ×0.01 A / I32, WR FC04 (optional block)derivednathanmarlor/foxess_modbus
39601 / 39603PV energy: total / todayU32, 0.01 kWhR FC04derivednathanmarlor/foxess_modbus
39605 / 39607Battery charge: total / todayU32, 0.01 kWhR FC04derivednathanmarlor/foxess_modbus
39609 / 39611Battery discharge: total / todayU32, 0.01 kWhR FC04derivednathanmarlor/foxess_modbus
39613 / 39615Grid export: total / todayU32, 0.01 kWhR FC04derivednathanmarlor/foxess_modbus
39617 / 39619Grid import: total / todayU32, 0.01 kWhR FC04derivednathanmarlor/foxess_modbus
39621 / 39623Yield: total / todayU32, 0.01 kWhread in the block, not usedderivednathanmarlor/foxess_modbus; docs/registers.md
39629 / 39631Consumption (inverter's load counter): total / todayU32, 0.01 kWhR FC04derivednathanmarlor/foxess_modbus
46001Remote control, a bit field: bit 0 on, bit 1 sign convention (0: + = discharge/export), bits 3:2 target (00 AC, 01 battery, 10 grid (CT/meter), 11 AC with grid first). OpenAmpere writes 5 (on with target battery) where 46007 is readable, otherwise 1 (on with target AC), and 0 (off); the previous smartbox writes 5. What the targets mean for grid charging: h3.md (#509)U16 bit fieldR FC03, W FC06confirmed (on/off); documented (bit field, changed in definition versions of 2024)nathanmarlor/foxess_modbus; FoxESS Modbus interface definition V1.05.04.00, table 3-8; #141, #196
46002Remote control watchdog timeoutU16, s (OpenAmpere 180, allowed 10–3600)R FC03, W FC06confirmednathanmarlor/foxess_modbus; #141, #196
46003–46004Remote control active powerI32, W, + = discharge/export, − = battery charges (sign not verified on every device)W FC16, R FC03 (diagnostics)confirmed (grid charging works)nathanmarlor/foxess_modbus; #196
46007Remote control timeout countdownU16, sR FC03 (read-only per FoxESS); OpenAmpere reads it on its own, a refusal tolerated: readable means the newer layout of 46001 (#509)documentedFoxESS Modbus interface definition V1.05.04.00, table 3-8
46501–46502Import limit (per foxess_modbus only on the H3 Smart)I32, Wnot usedderivednathanmarlor/foxess_modbus; docs/registers.md
46607Maximum charge currentU16, ×0.1 Aholding, writable; neither read nor written by OpenAmperederivednathanmarlor/foxess_modbus
46608Maximum discharge currentU16, ×0.1 Aholding, writable; neither read nor written by OpenAmperederivednathanmarlor/foxess_modbus
46609Outage floor (min_soc): lowest SoC in backup/off-grid operationU16, %R FC03, W FC06confirmed (0 % written via Modbus: open)nathanmarlor/foxess_modbus; #69, #72, #196
46610Charge limit (max_soc); not respected during forced chargingU16, %R FC03, W FC06confirmednathanmarlor/foxess_modbus; #196, #242
46611Backup reserve (min_soc_on_grid)U16, %R FC03, W FC06confirmed (also below 10 %)nathanmarlor/foxess_modbus; #196, #313
46616–46617Export (feed-in) power limitI32, W (OpenAmpere 0–99999 W and at most the rated power)R FC03, W FC16confirmednathanmarlor/foxess_modbus (H3 Smart); #196
49203Work mode: 1 self-use, 2 feed-in first, 3 backup, 4 peak shavingU16R FC03, W FC06confirmednathanmarlor/foxess_modbus; #196
20162Written as 1 by the previous smartbox; meaning unknown–neither read nor written by OpenAmpereopenreport in docs/registers.md

Behaviour

FactStatusSource
Reading with this map works on a real H3 (#11, #16). Not every register above is checked one by one; the reports name the exact variant only as "H3 / H3 Smart / H3 Pro / E3".confirmed#11, #16, #111, #173, #185
Control with this map works on a real system: work mode, backup reserve and limits, remote control for grid charging, export limit (earlier only partly confirmed, #25).confirmed#25, #196, #197
39141 is in 0.1 °C like the other temperatures: raw 452 means 45.2 °C, matching a second readout tool. Read without the factor, it exceeded the 120 °C plausibility limit and was dropped.confirmed#11, #26
37611 read about 15 °C above the cell temperatures on one owner's system and matched what another dashboard calls "BMS1 internal": it is the BMS electronics.confirmed#16, #41
The off-grid bit (39065 bit 0) was set in a single reading while the system exported several kW, followed by minutes without readings.confirmed#89, #90
The second battery module registers (38309, 38315, 38316) read 0 or the block is rejected when there is no second module.deriveddriver.py, diagnostics.py
The export limit register 46616 is rejected with "illegal address" on devices without it.deriveddriver.py
One device read about 60000 W in 46616, far above its rated power. Probably the value for "no limit set"; not confirmed against the manufacturer's app.opendiagnostics report, #413
On one owner's H3, 46001 stayed 1 with 46002 = 180 and 0 W long after the watchdog time; see h3.md.confirmed#141, #142
Reading 46001 right after writing 0 may show a delayed value; the delay is not quantified on a device (OpenAmpere polls for a few seconds). Under remote control a new backup reserve is taken over a few seconds late (#322).open#142, #322
On an EKD system with a second PV inverter, meter 2 read about as much as the H3's own PV while the battery charged at midday. The balance (PV + meter 2 + grid − battery charge) matched the house at 39225 only with meter 2 counted as positive generation: 39225 already contains the second inverter, 39118 does not.confirmed (one device)#635
Energy counters count in 0.01 kWh (10 Wh) units. Suspected: some newer firmware steps only by 0.1 kWh.open#194, #195

Decisions in OpenAmpere

DecisionWhyIssue/PR
Blocks 37002, 38309, 38901, 39063, 39118, 39141, 39279 and 39327 are optional: a rejected one is skipped.Models without a second battery, meter 2, MPPT details or other parts.registers.py
PV inputs: the MPPT trackers (up to 3) are preferred because they correspond to module arrays; otherwise PV1–PV4. PV total from 39118, otherwise the sum of the inputs.MPPTs match the owner's arrays.driver.py
While 38901 = 1, meter 2 (negative as 0) is the second PV inverter (pv_external_power), handled like Meter B of a SAJ (h2-family.md): counted as solar power only when the owner switches it on in "Meine Anlage", its energy integrated by OpenAmpere. The house stays 39225 either way.39118 and the PV counters leave it out; 39225 is measured and already contains it, so taking it out (as the SAJ balance does) would show too little house power while it is not counted. No energy counter for meter 2 is known.#635
SoC and battery temperatures are dropped when 37002 is 0; BMS2 temperatures are dropped when all are 0.No battery or no second module connected.driver.py
Grid power is negated to + = import.OpenAmpere's common sign convention.driver.py
If 46616 is rejected, the export limit is reported as not supported.Not every device has the register.driver.py
OpenAmpere's remote command pattern is 46001 = 5 (or 1, see h3.md) and 46002 = 180, with the power in 46003–46004; it recognises its own commands by it, 1 / 180 s left over by older versions included (#509).Release only what OpenAmpere started.#141, #142
Diagnostics (new map only): check the optional blocks 38309 and 39327; compare a 24-register block read at 37609 with single reads of 37609, 37612, 37624; check the scale of 39141 (raw values up to 90 count as ambiguous, the report shows raw and scaled value); show 37002 as yes/no.Finds block-read and scaling problems from a shared report.diagnostics.py, #19, #26, #44
Diagnostics read 46616 and report it rounded to 100 W with only the high word, not the raw words.The exact limit (60 % or 70 % of the kWp) reveals the system size.#149, #150
Diagnostics show a value above the rated power as information ("probably no limit set"), only a negative value as a warning.A device reported about 60000 W, far above its rated power; more than the rated power cannot be exported anyway.#413
Diagnostics read 46001–46004 as one FC03 block and tell three cases apart: off, on by OpenAmpere (charging or a leftover it switches off itself), on by another device (warning with the values). A background job reads the block read-only every 5 minutes to say how long it has been on. The check and the report decode 46001 (target, sign) and read 46007 on its own: a running countdown while OpenAmpere sends nothing means another writer or values restored after a restart, 0 while on means the watchdog left the switch on. 0 W is explained per target: the battery rests (target battery); the house runs from the grid and PV is curtailed once the battery is full (target AC) (#509).Shows who controls the battery, e.g. the previous smartbox.#126, #127, #135, #136, #142