Diese Seiten sind technisch und auf Englisch. Sie sammeln, was die Mitwirkenden von OpenAmpere über die Geräte herausgefunden haben, jeweils mit Quelle und wie sicher die Angabe ist. Sie zeigen den neuesten Stand der Entwicklung, der manchmal schon über deine installierte Version hinausgeht. Es sind keine offiziellen Angaben der Hersteller. Für die Einrichtung brauchst du sie nicht, die App erklärt dir alles Nötige.

my-PV AC ELWA heating rods

Not official manufacturer information. Compiled by the OpenAmpere contributors; can be incomplete or wrong. No affiliation with my-PV, not legal advice. See Device knowledge.

Applies to: my-PV AC ELWA-E, AC ELWA 2, AC THOR · Sold as: – (owners report a my-PV heating rod in EKD systems, connected through the IQ box; derived, Photovoltaikforum; an AC ELWA 2 connected to the box on one system (the box held its Modbus connection), confirmed, #660) · OpenAmpere: consumer type "my-PV heating rod", src/openampere/drivers/mypv.py (MyPvHeatingRod) · Support: display and control (power setpoint only) · Confirmed on a real device: display on one AC ELWA 2 (#660); control not yet

Summary

Registers

RegisterMeaningType, scale, signR/WStatusSource
1000Power setpointU16, WR/W (holding, FC03 read, FC06 write)documentedmy-PV Modbus TCP description; #238, #241
1001Water temperatureS16 (two's complement), 0.1 °C, e.g. 0xFFF6 = −1.0 °CRdocumented; read on one AC ELWA 2 (one of its two sensors, see Behaviour)my-PV Modbus TCP description; #241; #660
1002Target temperatureS16 (two's complement), 0.1 °CRdocumentedmy-PV Modbus TCP description; #241
1003Status, see belowU16, codeRdocumentedmy-PV Modbus TCP description; #238

Status codes of register 1003:

CodeMeaning
1not controlled
2heating
3standby
4boost heating
5water has reached the target temperature
9setup
20legionella protection
21switched off
22locked
200 and upfault (the value is the fault code)

Behaviour

FactStatusSource
Connection: Modbus TCP, port 502, unit id 1 (configurable).documentedmy-PV Modbus TCP description; docs/devices.md
The rod follows Modbus setpoints only while its control type is set to "Modbus TCP" in its web interface. A read that the rod rejects usually means another control type is set.documented (the hint about rejected reads: derived)my-PV Modbus TCP description; mypv.py
The rod has a control timeout set in its web interface: when no new setpoint arrives in time, it stops heating by itself. It has to be a little longer than OpenAmpere's interval.documentedmy-PV Modbus TCP description; #243
The manufacturer asks not to write any other register frequently, because they are kept in non-volatile memory.documentedmy-PV Modbus TCP description; NOTICE
The registers 1000–1003 do not contain the power the rod really takes; only the setpoint.derived#238
On an EKD system (with an SAJ inverter) the previous smartbox (Kiwigrid) held the rod's Modbus connection: OpenAmpere could read the rod only after the box was taken off the network and the rod restarted. Since then the box no longer reaches the rod. The water temperature is then shown.confirmed (one AC ELWA 2)owner report, #660
The AC ELWA 2 can have a second temperature sensor, mounted higher in the tank and therefore warmer. OpenAmpere shows only one temperature (1001); in which register the second one is, is open.confirmed (one AC ELWA 2; register open)owner report, #660

Decisions in OpenAmpere

DecisionWhyIssue/PR
Read 1000–1003 in one FC03 request; write only 1000, clamped to 0–65000 W, continuously by solar surplus (optionally with cheap grid power).Only the documented registers; the manufacturer asks not to write others.#238, #241, #262
Estimated power: the setpoint while the status is 2 or 4, or 3 with a setpoint above 0; otherwise 0.The rod's power is not available in these registers.#241
A temperature of 0 counts as not available; status 200 and up is shown as a fault with its code.0 is what an unset value reads.#241
Before the first write the rod is read once; OpenAmpere writes only if the status is 1–999 and both temperatures are within −30 to 120 °C.Register 1000 used to be written every few seconds to whatever address was entered; a wrong address (e.g. the inverter's) could be written outside its driver's checks.#259, #262
Only unit ids 1–247 are accepted; never 0.Unit id 0 is the Modbus broadcast: behind a gateway every device would take the write.#259, #262
A rod cannot be saved at the inverter's host and port. The resolved addresses are compared, so a host name and its IP address, or localhost and 127.0.0.1, count as the same device.The inverter must never be configured as a heating rod.#262, #351, #363
0 W is sent once to a rod OpenAmpere set to power when it is disabled, removed or changed, when control is switched off, when test mode is entered and when OpenAmpere stops; also with the master switch off or in test mode.Switching off is the safe direction; the rod's own timeout is only a second safeguard.#217, #224, #243, #247

Retries for an unreachable rod follow the rules for all consumers, see consumers.md.

Open questions

Sources