These pages are technical. They collect what the OpenAmpere contributors have found out about the devices, each fact with its source and how sure it is. They show the latest state of development, which can be ahead of the version you have installed. They are not official manufacturer information. You don't need them to set up OpenAmpere; the app explains everything you need.

FoxESS H3, register map of older firmware

Not official manufacturer information: compiled by the OpenAmpere contributors, possibly incomplete or wrong. Changing inverter settings can affect warranty and grid connection rules. No affiliation with FoxESS or EKD, not legal advice. See Device knowledge.

Applies to: classic FoxESS H3 with older firmware · Sold as: not stated in the sources (see h3.md) · OpenAmpere: driver foxess, register map foxess_h3_legacy · Support: display and control (no export limit) · Confirmed on a real device: no

Family facts (detection, connection limits, remote control behaviour, decisions on grid charging) are on h3.md; the newer map is on h3-new-map.md.

Summary

Registers

Read in blocks (start + count): 31000+52, 31090+1 (optional), 32000+24. Addresses inside a block that are not listed below are read but not used. Model string 30000–30015: see h3.md. All registers here are holding registers.

RegisterMeaningType, scale, signR/WStatusSource
30016–30018Firmware: master, slave, manager (on the new map these addresses hold the serial number)U16; shown as master/100, slave/100, manager in hexR (detected FC, then FC03, FC04)derivednathanmarlor/foxess_modbus; registers.py
31000 / 31001 / 31002PV1 voltage / current / powerI16, ×0.1 V / I16, ×0.1 A / I16, WR FC03derivednathanmarlor/foxess_modbus
31003 / 31004 / 31005PV2 voltage / current / powerI16, ×0.1 V / I16, ×0.1 A / I16, WR FC03derivednathanmarlor/foxess_modbus
31026 / 31027 / 31028Grid CT L1 / L2 / L3I16, W, + = exportR FC03derivednathanmarlor/foxess_modbus
31029 / 31030 / 31031Load L1 / L2 / L3 (no total register)I16, WR FC03derivednathanmarlor/foxess_modbus
31032Inverter temperatureI16, ×0.1 °CR FC03derivednathanmarlor/foxess_modbus
31033Ambient temperatureI16, ×0.1 °CR FC03derivednathanmarlor/foxess_modbus
31034Battery voltageI16, ×0.1 VR FC03derivednathanmarlor/foxess_modbus
31035Battery currentI16, ×0.1 AR FC03derivednathanmarlor/foxess_modbus
31036Battery powerI16, W, + = dischargingR FC03derivednathanmarlor/foxess_modbus
31037Battery temperatureI16, ×0.1 °CR FC03derivednathanmarlor/foxess_modbus
31038State of chargeU16, %R FC03derivednathanmarlor/foxess_modbus
31041Inverter state (status)U16R FC03derivednathanmarlor/foxess_modbus
31044 / 31045 / 31047Fault words, read as alarm words 1, 2, 3U16 eachR FC03derivednathanmarlor/foxess_modbus
31046, 31048–31051Further fault words (the fault words span 31044–31051)U16 eachread in the block, not usedderivednathanmarlor/foxess_modbus; docs/registers.md
31090State of health (SoH), only firmware 1.80 or newerU16, %R FC03 (optional block)derivednathanmarlor/foxess_modbus
32000 / 32002PV energy: total / todayU32 / U16, 0.1 kWhR FC03derivednathanmarlor/foxess_modbus
32003 / 32005Battery charge: total / todayU32 / U16, 0.1 kWhR FC03derivednathanmarlor/foxess_modbus
32006 / 32008Battery discharge: total / todayU32 / U16, 0.1 kWhR FC03derivednathanmarlor/foxess_modbus
32009 / 32011Grid export: total / todayU32 / U16, 0.1 kWhR FC03derivednathanmarlor/foxess_modbus
32012 / 32014Grid import: total / todayU32 / U16, 0.1 kWhR FC03derivednathanmarlor/foxess_modbus
32021 / 32023Load: total / todayU32 / U16, 0.1 kWhR FC03derivednathanmarlor/foxess_modbus
41000Work mode: 0 self-use, 1 feed-in first, 2 backup, 4 peak shavingU16R FC03, W FC06derivednathanmarlor/foxess_modbus
41001–41006Invalid: must not be read–never readderivednathanmarlor/foxess_modbus; docs/registers.md
41007Maximum charge currentU16, ×0.1 Aholding; neither read nor written by OpenAmperederivednathanmarlor/foxess_modbus
41008Maximum discharge currentU16, ×0.1 Aholding; neither read nor written by OpenAmperederivednathanmarlor/foxess_modbus
41009Outage floor (min_soc)U16, %R FC03, W FC06derivednathanmarlor/foxess_modbus
41010Charge limit (max_soc)U16, %R FC03, W FC06derivednathanmarlor/foxess_modbus
41011Backup reserve (min_soc_on_grid)U16, %R FC03, W FC06derivednathanmarlor/foxess_modbus
41012–41013, 41015Invalid: must not be read–never readderivednathanmarlor/foxess_modbus; docs/registers.md
44000Remote control on/offU16R FC03, W FC06derivednathanmarlor/foxess_modbus; #127
44001Remote control watchdog timeoutU16, sR FC03, W FC06derivednathanmarlor/foxess_modbus; #127
44002–44003Remote control active powerI32, W, + = discharge/export, − = battery chargesW FC16, R FC03 (diagnostics)derivednathanmarlor/foxess_modbus; #127

Behaviour

FactStatusSource
There is no total register for grid or house power, only the three phases; and only two PV inputs.derivednathanmarlor/foxess_modbus; docs/registers.md, docs/devices.md
Registers in the 41xxx range must be read one at a time; 41001–41006, 41012–41013 and 41015 are invalid.derivednathanmarlor/foxess_modbus; docs/registers.md
No register for the export limit is known on this map.deriveddocs/registers.md, docs/devices.md
The remote control block (on/off, timeout, power) sits at 44000–44003, the counterpart of 46001–46004 on the new map.derivednathanmarlor/foxess_modbus; #127
The energy counters count in 0.1 kWh (100 Wh) steps, so counter-based energy has no meaningful second decimal.derivednathanmarlor/foxess_modbus; #194, #195
Battery health (31090) needs firmware 1.80 or newer.derivednathanmarlor/foxess_modbus; docs/devices.md

Decisions in OpenAmpere

DecisionWhyIssue/PR
Grid power = −(31026 + 31027 + 31028) (+ = import), house power = 31029 + 31030 + 31031, PV power = PV1 + PV2.No total registers on this map.driver.py
31090 is an optional block: skipped if rejected.Older firmware has no SoH.registers.py
Battery settings are read one register at a time with FC03 (work mode, 41009, 41010, 41011).41xxx must be read individually.driver.py
No check that a new connection still reaches the same inverter: the map has no serial number to compare. A fixed IP address in the router matters even more here.The check needs a serial number (modbus.md).#567
The export limit is reported as not supported.No known register.driver.py
Counter step 100 Wh (energy_step_wh); counter-based energy is shown with one decimal.0.1 kWh counters.#194, #195
The FoxESS detail checks of the diagnostics (optional blocks, block reads, temperature scale, export limit, remote control) run only for the new map. The background job that watches the remote control (read-only, every 5 minutes) reads 44000–44003 on this map too.The detail checks are built on new-map addresses.diagnostics.py

Open questions

Sources