These pages are technical. They collect what the OpenAmpere contributors have found out about the devices, each fact with its source and how sure it is. They show the latest state of development, which can be ahead of the version you have installed. They are not official manufacturer information. You don't need them to set up OpenAmpere; the app explains everything you need.

SAJ H2, HS2, AS2 (family range of type codes)

Not official manufacturer information: compiled by the OpenAmpere contributors, can be incomplete or wrong. Changing inverter settings can affect the warranty and grid rules; no affiliation with SAJ or EKD; not legal advice. See the device knowledge README.

Applies to: SAJ hybrid inverters H2, HS2 and AS2, every type code 0x0050–0x006F in register 0x8F00 · Sold as: "Ampere.StoragePro" (H2, HS2 and the three-phase 0x005E; for the AS2 not stated in the sources) · OpenAmpere: driver saj (src/openampere/drivers/saj/), register map saj_h2 · Support: display for the whole family range; control (battery settings, export limit, grid charging) for 0x005A–0x005E since 0.29.0 · Confirmed on a real device: partly (identification, battery limits and battery temperature; in daily use on a 0x005E; the signs of battery and grid power not yet; of OpenAmpere's own writes only the on-grid depth 0x3644 on a 0x005E, which the battery keeps)

Type-specific page: 0x005E, "3P-X E2".

Summary

Registers

All reads use FC03, all writes FC06 (one register at a time). Device address (unit id) 1 or 2, port 502. "Community" means the projects listed under Sources.

Identification

RegisterMeaningType, scale, signR/WStatusSource
0x8F00Device type code. Names: 0x0055 "AS2 3-6K", 0x0056 "AS2 5-10K", 0x005A "H2 3-6K S2", 0x005B "H2 5-10K S3", 0x005C "HS2 3-6K S2", 0x005D "HS2 5-10K S3", 0x005E "3P-X E2" (not in the protocol, see its page)U16RconfirmedH2 protocol (0x0055–0x005D); community; read on a real 0x005E (#334, #339, #379)
0x8F01Rated power; used for the export limit and the charging power in %U16, WRopenOpenAmpere's reading since #379, without a source; stanus74 names it "sub type" (#492)
0x8F02Communication version (read with the block, not shown)U16Rderivedcommunity
0x8F03–0x8F0CSerial number10 registers ASCIIRderivedcommunity
0x8F0D–0x8F16Product code; shown as serial number if the serial is empty10 registers ASCIIRderivedcommunity
0x8F17–0x8F1CFirmware versions; the first three are shown as value / 10006 × U16Rderivedcommunity

Status, clock and temperatures

RegisterMeaningType, scale, signR/WStatusSource
0x4000–0x4003Inverter clock: year; month << 8 | day; hour << 8 | minute; second << 8. Charge slots follow this clock4 × U16RdocumentedH2 protocol; #377, #378
0x4004Running mode: 0 init, 1 wait, 2 run, 3 off-grid (power cut), 4 on-grid storage, 5 fault, 6 update, 7 test, 8 self-check, 9 reset. Also part of the detection checkU16Rderivedcommunity
0x4005–0x4006Fault word 1U32Rderivedcommunity
0x4007–0x4008Fault word 2U32Rderivedcommunity
0x4009–0x400AFault word 3U32Rderivedcommunity
0x4010Inverter (heat sink) temperatureI16, ×0.1 °CRderivedcommunity
0x4011Ambient temperatureI16, ×0.1 °CRderivedcommunity

Read-back of the battery settings

RegisterMeaningType, scale, signR/WStatusSource
0x4022Work mode (AppMode) read-back; used for the work mode only if 0x3644–0x3647 cannot be readU16Rderivedcommunity
0x4029Charge limit read-back; used only if 0x3644–0x3647 cannot be read. Which setting it mirrors was not established by the report in #334U16, % SoCRopencommunity; #334, #337
0x402A"BatDisSocDowLimit" / set SoC_L: on-grid limit (backup reserve) read-back; used only if 0x3644–0x3647 cannot be read. Equalled 0x3644 on a real device. Up to 0.25.0 it was wrongly read as the off-grid limitU16, % SoCRconfirmedH1 protocol (applies to grid-connected operation); #334, #335
0x402BLabelled "dod" in the diagnostics report; read only there, meaning unknownU16, %R (diagnostics)open#337
0x402C"BatResSoc", reserved SoC: read with the block but not used. Up to 0.25.0 it was wrongly read as the backup reserveU16, % SoCRopencommunity; #334, #335

Battery, PV and power

RegisterMeaningType, scale, signR/WStatusSource
0x4069Battery voltageU16, ×0.1 VRderivedcommunity
0x406ABattery currentI16, ×0.01 ARderivedcommunity
0x406EBattery temperature (fallback 0xA010)I16, ×0.1 °CRconfirmedcommunity; matched another integration on a real device (#372, #376)
0x406FState of charge; also part of the detection check (≤ 10000)U16, ×0.01 %Rderivedcommunity
0x4071 / 0x4072 / 0x4073PV1 voltage / current / powerU16 ×0.1 V / U16 ×0.01 A / U16 WRderivedcommunity
0x4074 / 0x4075 / 0x4076PV2 voltage / current / poweras PV1Rderivedcommunity
0x4077 / 0x4078 / 0x4079PV3 voltage / current / poweras PV1Rderivedcommunity
0x407A / 0x407B / 0x407CPV4 voltage / current / poweras PV1Rderivedcommunity
0x40A0House consumption as the inverter computes it. On one device it matched the balance (grid + PV + Meter B + battery, #419); on a 0x005E with a second inverter at Meter B it was far off while the battery charged or discharged (about 0.5 kW too high while charging at about 1 kW, half the balance while discharging). OpenAmpere uses it only as a fallbackI16, WRderivedcommunity; #576
0x40A3Power measured by a second meter at the inverter (Meter B, "CT PV power"): an extra PV inverter without its own connection. Not part of 0x40A5; on one device the balance only closed with it. Negative values (standby at night, meter direction) are counted as 0.I16, WRderivedstanus74/home-assistant-saj-h2-modbus ("CT_PVPowerWatt"); one owner's measurements, #419
0x40A5PV power of the inverter itself, total (if missing, the sum of PV1–4); without Meter B (0x40A3)I16, WRderivedcommunity
0x40A6Battery power. On a 0x005E the state of charge rose while it was negativeI16, W, + = dischargingRderivedevcc-io/evcc saj-h2 template; an owner's app screenshots in #576
0x40ADGrid power (system meter). On a 0x005E it was positive in the evening without PV and with the battery idleI16, W, + = importRderivedevcc-io/evcc saj-h2 template; an owner's app screenshots in #576

Energy counters

All U32 (two registers), 0.01 kWh (OpenAmpere: ×10 → Wh, counter step 10 Wh).

RegisterMeaningType, scale, signR/WStatusSource
0x40BF / 0x40C5PV energy today / total. Whether it covers all MPPTs is openU32, 0.01 kWhRderivedcommunity
0x40C7 / 0x40CDBattery charge today / totalU32, 0.01 kWhRderivedcommunity
0x40CF / 0x40D5Battery discharge today / totalU32, 0.01 kWhRderivedcommunity
0x40DF / 0x40E5House consumption today / totalU32, 0.01 kWhRderivedcommunity
0x40EF / 0x40F5Grid export today / total, phase L1 (SAJ calls it "sell")U32, 0.01 kWhRderivedcommunity
0x40F7 / 0x40FDGrid import today / total, phase L1 (SAJ calls it "feed-in")U32, 0.01 kWhRderivedcommunity
0x4167 / 0x416DGrid import today / total, all three phases; missing on some firmwareU32, 0.01 kWhRderivedcommunity
0x416F / 0x4175Grid export today / total, all three phases; missing on some firmwareU32, 0.01 kWhRderivedcommunity

Battery modules (BMS)

RegisterMeaningType, scale, signR/WStatusSource
0xA000Number of battery modules (read with the block, not used)U16Rderivedcommunity
0xA00DBattery state of healthU16, ×0.01 %Rderivedcommunity
0xA010Temperature of the first battery module; fallback for 0x406EI16, ×0.1 °CRderivedcommunity; #376

Settings and control

RegisterMeaningType, scale, signR/WStatusSource
0x3604Charge slot enable mask: bit n switches charge slot n+1 on. OpenAmpere uses bit 6 (slot 7)U16, bit maskR/WdocumentedH2 protocol; stanus74 charge_control.py; evcc saj-h2.yaml; #377
0x3606–0x3617Charge slots 1–6 (three registers each, layout as slot 7). Not read or written by OpenAmpere; stanus74 and evcc use slot 1 (0x3606–0x3608)3 × U16 per slot–documentedH2 protocol; stanus74; evcc
0x3618Charge slot 7 start: hour << 8 | minuteU16R/WdocumentedH2 protocol; #378
0x3619Charge slot 7 end: hour << 8 | minuteU16R/WdocumentedH2 protocol; #378
0x361ACharge slot 7 days (high byte, bit 0 = Monday) and power in % of rated power (low byte)U16R/WdocumentedH2 protocol; #378
0x3636–0x363APassive mode registers. Not read or written: no timeout (see Behaviour)––documentedH2 protocol; stanus74/home-assistant-saj-h2-modbus#157
0x3644On-grid discharge depth = backup reserve, lowest SoC in normal operation (self-use). In % SoC, not depth of discharge. Matched the manufacturer's app on a real device; the previous IQ box writes it as the reserve. OpenAmpere's write and read-back confirmed on a 0x005E, and the battery kept to the new valueU16, % SoCR/WconfirmedH2 protocol; stanus74 (name); #334, #335, #337; stanus74/home-assistant-saj-h2-modbus#18; #601, #615
0x3645Off-grid discharge depth: lowest SoC during a power cut. In % SoC. Matched the manufacturer's app on a real device; OpenAmpere's write not yet confirmedU16, % SoCR/WconfirmedH2 protocol; stanus74 (name); #334, #335, #337
0x3646Charge limit (highest SoC). Read on a real device as part of the block; OpenAmpere's write not yet confirmedU16, % SoCR/WdocumentedH2 protocol; stanus74 charge_control.py; evcc saj-h2.yaml; #334, #378
0x3647Work mode (AppMode): 0 self-use, 1 time-of-use, 2 backup, 3 passive, 10 peak shaving. Read on a real device as part of the blockU16R/WdocumentedH2 protocol; stanus74; evcc; #334, #377
0x3651"BatSocLimitkeep": reserve that applies in work mode backup (AppMode 2). On a real device it held a value of its own, different from 0x3644U16, % SoCR/WdocumentedH2 protocol; evcc saj-h2.yaml; #334, #380, #381
0x365AExport limit in per mille of the rated power; applies only while 0x365C is 1 or 3U16, ‰ of 0x8F01R/Wdocumented (register, mode); derived (unit: the per-mille formula is given for the neighbouring percentage registers, and its base 0x8F01 is open)H2 protocol; stanus74; evcc; #377, #492
0x365BExport limit by phase current, used with 0x365C = 2. Read with 0x365A–0x365C, never writtenU16, ARdocumentedH2 protocol; #378
0x365CExport limit ("anti-reflux") mode: 0 off, 1 total power, 2 phase current, 3 power per phaseU16R/WdocumentedH2 protocol; #377
0x365FTime-of-use behaviour outside the charge slots: 0 standby, 1 self-useU16R/WdocumentedH2 protocol; #378
0x8300–0x8306Undocumented block; answers reads; the previous IQ box writes it every 1–3 s while charging. Not read or written by OpenAmpere––openstanus74/home-assistant-saj-h2-modbus#18; research in #377

Behaviour

FactStatusSource
Modbus TCP on port 502; the device address is 1 or 2, depending on the installation (communication module).derivedcommunity; devices.md
EKD's SAJ systems ("Ampere.StoragePro", 2023–2024) come with a Chint DTSU666 grid meter, sold as "AMPERE.StoragePro Meter" and connected to the inverter over RS485.derivedPhotovoltaikforum on the Ampere Storage Pro; names.md
Names and meanings of the live registers were checked against SAJ's protocols for related inverters (R5/R6/C6 and H1).derivedregisters.md
SAJ's H2 protocol lists the type codes 0x0055–0x005D; 0x005E is not in it.documentedH2 protocol; #379
A type code does not identify one power class: 0x005B covers 5 to 10 kW.documentedH2 protocol; #379
On a real device (type 0x005E) detection, live values and battery limits read correctly with this map.confirmed#334, #339
The AS2 (0x0055, 0x0056) is read with the same map; no report from a real AS2 yet.open#347, #348, #378
Running mode 3 (0x4004) means off-grid: the inverter supplies the house during a power cut.derivedcommunity
The summed grid counters 0x4167 ff. are missing on some firmware (the block is rejected).derivedcommunity; devices.md
SAJ's counter names are the wrong way round from the owner's view: export is "sell", import is "feed-in".derivedcommunity
The battery limits are 0x3644 (on grid, = backup reserve) and 0x3645 (off grid, during a power cut), both in % SoC. Turned out wrong: up to 0.25.0 OpenAmpere read the reserve from 0x402C and the off-grid limit from 0x402A, so on a real device the two values appeared swapped compared with the manufacturer's app.confirmed#334, #335, #337
The block 0x3644–0x3647 (on-grid depth, off-grid depth, charge limit, work mode) matched the manufacturer's app on a real device.confirmed#334 (diagnostics report), #337
Some firmware rejects 0x3644–0x3647; then only the read-back registers 0x4022, 0x4029 and 0x402A are available.derived#335, #337
In the read-back block of that device 0x402A equalled 0x3644. 0x402C equalled the off-grid depth and not 0x3651, but the off-grid depth had a value an unused register could also show, so this does not settle 0x402C.confirmed (0x402A), open (0x402C)#334, #335, #337
Battery temperature 0x406E matched the value of another integration on a real device. (An earlier question whether this value is the battery or the BMS temperature, #41, is settled by this.)confirmed#372, #376
SAJ has no "feed-in first" work mode; the modes are self-use, time-of-use, backup, passive and peak shaving.documentedH2 protocol; #377
0x3651 is the reserve of the backup mode. On a real device it held a different value than 0x3644, so the two are separate settings. The backup mode keeps the battery full for a power cut only if 0x3651 is 100 %.documented; confirmed (separate register)H2 protocol; #334, #380
In backup mode the battery supplies the house only down to 0x3651 and keeps the rest for a power cut; 0x3644 has no effect in that mode. evcc relies on this (backup mode with 0x3651 = lowest SoC for normal operation, = highest SoC to hold the battery).openH2 protocol; evcc saj-h2.yaml; #380, #381
0x365A limits the export only while 0x365C is 1 (total power) or 3 (per-phase power); with 0 there is no limit, with 2 the limit is a phase current in 0x365B.documentedH2 protocol; stanus74 (register overview); #377, #492
SAJ has no remote control that ends by itself: the H2 protocol defines no timeout for passive mode (0x3636–0x363A), and owners report that passive mode stays on for hours after one write.documented (no timeout), derived (owners)H2 protocol; stanus74/home-assistant-saj-h2-modbus#157; #377
No public SAJ document (H2 protocol, H1, AS1, R5/R6/C6) has a timeout, watchdog or validity field for passive mode or any power command. SAJ reportedly has an "External Dispatch / EMS control" specification for professional partners only, which OpenAmpere cannot use.documented (none in public documents), derived (partner specification)H2 protocol; stanus74/home-assistant-saj-h2-modbus#199 (discussion); research in #377
Time-of-use charging: AppMode 1, seven charge slots of three registers each from 0x3606 (slot n at 0x3606 + 3 × (n−1)), each with start, end, day mask and power in %, switched on per slot by a bit in 0x3604. Outside the slots the inverter follows 0x365F.documentedH2 protocol; #377
Charge slots run on the inverter's clock (0x4000), not on the clock of the computer OpenAmpere runs on.documentedH2 protocol; #378
A slot with a day mask repeats every week until it is switched off or deleted.derived#378
evcc's saj-h2 template controls the battery only through stored settings: normal = backup mode with 0x3651 = lowest SoC, hold = backup mode with 0x3651 = highest SoC, charge = AppMode 1 with 0x3604 = 1 and slot 1 over the whole day at 100 %. No watchdog (unlike its FoxESS H3 template).derivedevcc-io/evcc templates/definition/meter/saj-h2.yaml; research in #377
stanus74's "Charging Control" switch sets bit 0 of 0x3604 (slot 1) and AppMode 1, and on switching off writes 0x3604 = 0 and the previous AppMode; the owner sets the slot times. The switch counts as on only with bit and AppMode together.derivedstanus74/home-assistant-saj-h2-modbus charge_control.py, switch.py at e83bfb5; research in #377
The previous IQ box writes 0x3647 and 0x3644, and the block 0x8300–0x8306 every 1–3 s while charging. Whether 0x8300–0x8306 ends by itself (the only candidate for a remote control with a timeout) has not been tested.derivedstanus74/home-assistant-saj-h2-modbus#18; #377
When the box writes 0x8300 at the start of a charge, 0x3647 changes to 3 (passive mode) by itself; at the end the box writes 0x8300 = 0 and 0x3647 = 0 back to back. 0x8300 is in no public SAJ document and no other project uses it; nobody has published a meaning for 0x8304 = 600.derivedstanus74/home-assistant-saj-h2-modbus#18 (recorded traffic), stanus74/home-assistant-saj-h2-modbus#19 (research only)
The inverter keeps running without the IQ box and without any other controller: owners report it running on with the box switched off, or never having had one. No public SAJ document has a function that stops or limits the inverter when an external controller falls silent; a lost meter ("Meter Communication Lost") is listed as a warning, not a fault, in the error table of the H2 user manual, without a stated effect on the export. See iq-box.md.confirmed (owner reports), documented (none in public documents)owner reports linked on iq-box.md; H2 user manual (see Sources)
Another device (the IQ box, the SAJ app) can set the work mode away from time-of-use or clear bit 6 of 0x3604 while OpenAmpere charges through slot 7; the slot then no longer charges.derived#382, #383; stanus74/home-assistant-saj-h2-modbus#18
Writing 0x3644–0x3647 with FC06, one register at a time, is how the H2 protocol, stanus74 and evcc do it. Reading these registers is confirmed on a real device; OpenAmpere's writes were not yet confirmed on a real device when control was added.documentedH2 protocol; stanus74; evcc; #378
Reading is confirmed on a real 0x005E ("3P-X E2"), and an owner uses OpenAmpere on one in daily operation without problems; whether control was switched on and which writes were made is not recorded. Another owner then changed the on-grid depth 0x3644 from the app; the inverter accepted it, OpenAmpere read it back and the battery kept to it. The other writes are not confirmed. Nothing is confirmed on 0x005A–0x005D. README and website once showed a checkmark for all of SAJ, corrected to "not yet confirmed" and later to this state.confirmed (reading and daily use on 0x005E, write of 0x3644 and the battery keeping it), open (other writes, rest)an owner's report (2026-10); #111, #173, #185, #469, #601, #615; devices.md
On one 0x005E the previous IQ box kept the inverter's Modbus TCP connection busy all the time, so OpenAmpere could not connect while the box was in the network. After the box was cut from the network, OpenAmpere detected the inverter and read live values a few minutes later.confirmed (on 0x005E)owner report by e-mail on a 0x005E, summarised in #469; #311
On another 0x005E OpenAmpere ("Nur ansehen", connection mode "per poll", a reading every 30 s) read live values over Modbus TCP for days while the box stayed connected and controlled the system, also for about two hours in which the box had no cloud connection. Why it worked there and not on the device of #469 is open.confirmed (one 0x005E)owner report in #576
On one 0x005E read by OpenAmpere and another Modbus client at the same time, the inverter's network cable was unplugged for several minutes. Afterwards the other client read again, OpenAmpere not until it was restarted. Among the last disconnects in its diagnostics report the inverter twice accepted a connection and closed it right away (the sign of all connections taken, #311); which of them belong to that outage the report does not show. Likely: the inverter still held the old, half-open connection, and the other client took the remaining one. The connection option "free blocked access after a dropout" (#644) is meant for this; not tried on an SAJ yet.openowner's message and diagnostics report, #640

Decisions in OpenAmpere

DecisionWhyIssue/PR
Detection after FoxESS (unit 247): SAJ at unit 1, then 2. Block 0x8F00 (29 registers), then a plausibility check: 0x4004 ≤ 9 and 0x406F ≤ 10000.The address depends on the installation; the check rejects devices that answer 0x8F00 but are no SAJ hybrid.initial driver; devices.md
Known codes get their name; other codes in 0x0050–0x006F are accepted with a warning in the log, read like an H2 and shown as "Typ 0x…"; codes outside the range are rejected.New family members can be read without a release; a foreign device is not mistaken for an SAJ.initial driver; #379
Register map saj_h2, driver label "SAJ H2 / HS2"; the rated power comes from 0x8F01, not from the model name.One type code covers several power classes.#379
0x8F01 counts as rated power only within the power class in the name of the type (0x0055–0x005D, e.g. "5-10K": 5 to 10 kW). Otherwise (outside the class, 0x005E, an unknown type) the export limit is written only after the owner confirmed the rated power from the type plate in the app, also a lower one; the confirmed value is then the base of the per-mille conversion and of the charging power, as long as the device reports the value it was confirmed for.The meaning of 0x8F01 has no source, and a wrong base makes the export limit wrong by the same factor while the read-back still matches.#492
The live blocks are read with every poll: 0x4004 (14), 0x4022 (11), 0x4069 (20), 0x40A0 (14), 0x40BF (64), 0x4167 (16), 0xA000 (18). A block the device rejects is skipped.Optional blocks (summed counters) must not break the reading.initial driver
Meter B (0x40A3) is read with every poll (it is in the block 0x40A0) but counted as solar power only when the owner switches on the second inverter in "Meine Anlage"; it is then shown as its own source. The app points to the switch when the meter reads power.Not every system uses Meter B for an extra PV inverter, and the owner can name it.#419
The live house power is the balance grid (0x40AD) + PV (0x40A5) + Meter B (0x40A3, negative as 0) + battery (0x40A6), at least 0; 0x40A0 only when one of them is missing or not real. Meter B is taken out again when the owner does not count the second inverter, so the house matches the solar power and the stored energy (which leave Meter B out then too). Confirmed on a 0x005E with a second inverter at Meter B while the battery charged and discharged (#576).0x40A0 did not match the balance on every device; the energy values already come from the balance (#346). Meter B is not always an extra PV inverter.#576
No energy counter for Meter B is known: OpenAmpere integrates its power (not across gaps over 2 minutes) into a counter of its own. The quarter hours add it to PV (and so to the consumption) and keep it in pv_external; Home Assistant gets it as its own lifetime counter.Without it, generation, consumption, self-sufficiency and savings would be too low.#419
Grid counters: the summed counters (all phases) if the device has them, otherwise L1. The source is fixed after the first reading.Switching between them would look like a huge energy jump.initial driver; devices.md
Energy counters are treated with a 10 Wh step (0.01 kWh).Resolution of the SAJ counters; the app shows the matching decimals.#194, #195
0x3644–0x3647 are read only for the battery settings, not with every poll; a rejected read is remembered. Without them the on-grid limit comes from 0x402A, the charge limit from 0x4029, the work mode from 0x4022; the off-grid limit stays unknown.Firmware that rejects them cannot break the live values; no guessed limit.#335, #337
0x402C is not used.Its meaning is not certain (see Behaviour).#335
Diagnostics check "Speicher-Grenzen (SAJ)" shows 0x3644–0x3647, 0x3651 and 0x4029–0x402C side by side; owners compare them with the manufacturer's app.To confirm which register holds which limit.#334, #337
Control only for 0x005A–0x005E (battery settings, export limit, grid charging), with the same checks as FoxESS (master switch, test mode, limits, read-back, control log). AS2 and other codes stay read-only. Before 0.29.0 the SAJ driver was read-only; control was planned only after verification on real devices.H2 and HS2 are in the protocol and controlled the same way by stanus74 and evcc; 0x005E's settings matched the manufacturer's app. No evidence for the AS2.#113, #211, #377, #378
Work modes offered: self-use (0) and backup (2) only; other modes are refused.Time-of-use is OpenAmpere's own tool for grid charging, passive belongs to external controllers, peak shaving is not needed.#377, #378
A work mode changed while OpenAmpere charges (AppMode temporarily 1) is stored and applied when charging ends; the settings show the owner's mode, not time-of-use.Writing it right away would stop the charging.#378
Limits: charge limit 10–100 %; reserve and off-grid limit by the common rules (off-grid limit from 0 %, reserve at least 10 %, lower only with the owner's confirmation, #313).Same rules as FoxESS.#69, #313, #378
0x3651 is shown and set as "Reserve im Modus Notstromreserve" while the work mode is backup: 10–100 %, not above the charge limit, with test mode, read-back, control log and overwrite check. Home Assistant gets a backup_soc number only when the device reports it.In backup mode it is the reserve that applies; FoxESS has no such setting.#380, #381
Export limit: written rounded down to the per-mille step (step = rated power / 1000, rounded up, shown in the app); a read-back up to one step below the request counts as the same limit. The limit is written before the mode; if 0x365C is not 1 or 3 it is set to 1. With 0x365C = 0 the limit counts as the rated power; 0x365C = 2 is shown as not supported and nothing is written. 0x365C is read and shown. Legal checks and confirmations are the FoxESS ones.Never more feed-in than set; a limit that does not apply must not look like one that does.#377, #378
Grid charging through a short charge slot of the time-of-use mode, not passive mode. The issue planned slot 1; the implementation uses slot 7 (0x3618–0x361A, bit 6 of 0x3604).Passive mode would keep charging after OpenAmpere stops; a slot ends by itself. Slot 7 leaves the owner's slots (usually the first) alone. This is the documented exception to "continuous control only via a remote control with a watchdog" (AGENTS.md).#377, #378
The slot covers today from now for 10 minutes (never past 23:59; the next day gets a new slot) and is extended when fewer than 5 minutes are left; only the end moves, so a stored register is written about every 5 minutes. Power = rated power × % rounded up, 1–100 %.If OpenAmpere stops, charging ends at most 10 minutes later; few writes to stored registers.#377, #378
Start order: slot registers, 0x365F = 1, bit 6 of 0x3604, AppMode 1 last. With every command, 0x365F, the bit and AppMode are set again where they differ, and a slot changed while switched off is written again.The slot holds OpenAmpere's values before it is switched on; like the FoxESS remote control, OpenAmpere takes over again after another device changed something.#378, #382, #383
The owner's AppMode, 0x365F and slot-7 words are kept in the remote_command meta from the start of a session (also when someone changes them in between) and put back when charging ends, also after a restart. A work mode the owner chooses while OpenAmpere charges is not written but kept for the end of charging, and stored in the meta right away (#493). After a restart, before the first charging command, the kept values are taken over from the meta while slot 7 still holds OpenAmpere's words, is on and AppMode is 1; otherwise the new mode is written right away (#497). The takeover also happens when the app reads the settings, so it shows the owner's mode instead of none (#500).Before #383 a slot switched off by another device made the next command look like a new start, AppMode 1 was stored as the owner's mode and the inverter stayed in time-of-use after charging.#378, #382, #383
Slot 7 is never taken over while it is switched on with other values (the app says to free it in the SAJ app). Release only while slot 7 still holds OpenAmpere's values: clear bit 6, put back AppMode (if 1), 0x365F and the owner's slot words, then check that bit 6 is off.Release only what OpenAmpere started.#378, #383
OpenAmpere's new slot words are kept before they are written. While a slot write may have been cut off (written, but the answer timed out), each slot word may be the one before or OpenAmpere's new one and the slot still counts as OpenAmpere's; the remote_command meta keeps this also after a failed command, so a release after a restart puts the owner's slot back as well.A write that reached the inverter without an answer would otherwise leave a weekly grid charge switched on.#491
The inverter clock (0x4000) is read before each charging command; an implausible clock (no valid date) stops the command. The issue planned to refuse a clock that is far off; the code does not compare it with real time.The slot follows the inverter's clock.#377, #378
AppMode 3 (passive) is reported as "another device controls the inverter".Only external controllers use passive mode.#378
The charging page says that charging can go on up to 10 minutes after OpenAmpere stops, and that the slot repeats weekly until OpenAmpere runs again or it is deleted in the manufacturer's app.The owner must know what stays on the inverter.#378
0x8300–0x8306 is not used.Undocumented and untested.#377
Diagnostics check "Steuerung (SAJ)": slot 7 on/off, its length and power (no times or days), 0x365F, 0x365A/0x365C and whether the clock is readable (not the time).Times and days would tell when the owner charges.#378

Open questions