These pages are technical. They collect what the OpenAmpere contributors have found out about the devices, each fact with its source and how sure it is. They show the latest state of development, which can be ahead of the version you have installed. They are not official manufacturer information. You don't need them to set up OpenAmpere; the app explains everything you need.

Solarmax MAX.STORAGE ("AMPERE.Storage")

Not official manufacturer information: compiled by the OpenAmpere contributors, can be incomplete or wrong. Changing inverter settings can affect the warranty and grid rules; no affiliation with Solarmax or EKD; not legal advice. See the device knowledge README.

Applies to: Solarmax MAX.STORAGE and MAX.STORAGE Ultimate hybrid inverters · Sold as: "AMPERE.Storage" (EKD, the 10 kW Ultimate, about 2022–2023) · OpenAmpere: driver solarmax (src/openampere/drivers/solarmax/), register map solarmax_max_storage · Support: display only · Confirmed on a real device: partly (detection, live values and the grid sign from a diagnostics report, zeros in the "Connectivity+" registers on two devices; the battery sign from the energy balance of one report)

Summary

Registers

All input registers (FC04), unit id 1. 32-bit values: low word at the lower address.

RegisterMeaningType, scale, signR/WStatusSource
100–101Serial number of the control unitU32RdocumentedSolarmax list
102Firmware of the control unit, e.g. 344 = 3.4.4U16RdocumentedSolarmax list
103Device state: 0 unknown, 1 ok, 2 warning, 3 errorU16RdocumentedSolarmax list
105Nominal AC powerU16, WRdocumentedSolarmax list
110–111PV power (DC) of this inverterI32, WRdocumented, derived (type)Solarmax list; evcc
112–113PV power (DC) of the whole plant, other connected inverters includedI32, WRdocumentedSolarmax list
114–115Battery power, + = charging, − = dischargingI32, WRdocumented, derived (type, sign)Solarmax list; evcc (scale −1); #647
116–117House consumption ("Eigenverbrauchsleistung")I32, WRdocumentedSolarmax list
118–119Grid power, + = export, − = importI32, WRdocumented, derived (type), confirmed (sign)Solarmax list; evcc (scale −1); #596
120–121AC power of the whole PV plantI32, WRdocumentedSolarmax list
122State of chargeU16, %RdocumentedSolarmax list; evcc
123Usable battery capacityU16, whole kWhRdocumentedSolarmax list
124Energy stored nowU16, whole kWhRdocumentedSolarmax list
125, 126Power of MPPT 1 and 2U16, whole kWRdocumentedSolarmax list
130–138Battery limits, pack voltages, cell temperatures ("Connectivity+")RdocumentedSolarmax list
140–143AC voltages L1–L3, grid frequency ("Connectivity+")RdocumentedSolarmax list
150–151PV energy of this inverter and those connected to it ("Connectivity+")U32, whole kWhRdocumentedSolarmax list
152–153Energy exported to the grid ("Connectivity+")U32, whole kWhRdocumentedSolarmax list
154–155Energy imported from the grid ("Connectivity+")U32, whole kWhRdocumentedSolarmax list
156–157Energy charged into the batteries ("Connectivity+")U32, whole kWhRdocumentedSolarmax list
158–159Energy discharged from the batteries ("Connectivity+")U32, whole kWhRdocumentedSolarmax list
holding 140–143Battery power setpoint, watchdog, active power limit in % ("Connectivity+")R/Wdocumented; not used by OpenAmpereSolarmax list

"Solarmax list" is "MAX.STORAGE / MAX.STORAGE Ultimate ModbusTCP Datenpunktliste" (2024-09-11, firmware 3.4.4 and later). The input registers 140–143 and the holding registers 140–143 are different tables.

Behaviour

FactStatusSource
Solarmax's list marks 100–126 as available on every device and 130–159 as "Connectivity+" only.documentedSolarmax list
evcc reads grid 118, PV 110, battery 114 and state of charge 122 as signed 32-bit values with the low word first, and dropped the PV energy register because it counts only whole kWh. Battery control in evcc needs "Connectivity+" and firmware 3.4.4.derivedevcc-io/evcc templates/definition/meter/solarmax-maxstorage.yaml at 8796395558 (MIT)
Tinkerforge's energy manager reads the same addresses and also 112, 116 and 120: a second, independent reading of these registers.derivedTinkerforge/esp32-firmware software/src/modules/meters_modbus_tcp/solarmax.py (LGPL-2.1, facts only)
geeks-r-us/solarmax2mqtt reads the device over Modbus TCP; geeks-r-us/maxstorage_ultimate reads the web interface on port 80 instead (no license: facts only). The older Solarmax "MaxTalk" protocol (port 12345) belongs to Solarmax string inverters, not to MAX.STORAGE.derivedthe repositories named (solarmax2mqtt MIT)
The web interface shows firmware, hardware version and an "Ident"; the device can be reached as <Ident>.local.derivedgeeks-r-us/maxstorage_ultimate
The list defines holding registers 140/141 as one 32-bit setpoint; evcc writes them as two 16-bit limits with 142 as watchdog, which owners say works. Only matters for control.openSolarmax list; evcc template
Solarmax is in preliminary insolvency proceedings since 2024-11-29 (court Neu-Ulm); no buyer is reported.documentedsolarserver.de, 2024-12-06
The app and the device's web interface keep working inside the home network by IP address; the cloud portal came back in 2025 as a paid subscription run by another company, and the old Solarmax apps are no longer in the App Store.derivedphotovoltaikforum.com threads 243977 and 252527 (2025); research in #519
EKD switched the storage function off remotely in September 2025 and released it after a fuse was fitted in the battery line. How the registers look while it is switched off is not known.derived (shutdown), open (registers)names.md; photovoltaikforum.com thread 252527
"AMPERE.Storage" is the 10 kW variant (three-phase, 2 MPPT, 6–15 kWh in 3 kWh packs); MAX.STORAGE Ultimate also exists with 6, 8, 12 and 15 kW, and the list covers the older MAX.STORAGE too. Register 105 tells them apart.documentedEKD datasheet "AMPERE.Storage" (2022-07); Solarmax datasheet MAX.STORAGE Ultimate (2021-12)
On the first owner's device (OpenAmpere 0.41.0, Docker) detection at unit 1 over port 502 with FC04 worked and 100–126 read. With no PV and the battery idle, the diagnostics showed grid power of about −3 kW and the same house power in Solarmax's signs: 118 is negative for import, as the list says. The "Connectivity+" registers 130–143 and 150–159 answered with zeros, not with an exception, so this device has no energy history. The owner says the directions of the flows are right as far as they could tell.confirmed (detection, live values, grid sign, zeros without "Connectivity+"), open (battery sign)owner's diagnostics report by e-mail, summarised in #596
On a second owner's device (an EKD unit, firmware within the list's range, OpenAmpere 0.41.0) the diagnostics again showed the live values read and the "Connectivity+" registers 130–143 and the counters 150–159 answering with zeros. Before #636 OpenAmpere therefore had no energy history and every day value stayed at 0, while the live values were right. In the same reading PV covered the house with a little left over, and both 114 (battery) and 118 (grid) were small and positive: charging and export in Solarmax's signs, as the list says. The values are rounded to 100 W, so this is weak evidence for the battery sign.confirmed (zeros without "Connectivity+" on a second device), derived (battery sign, one rounded reading)owner's diagnostics report in #636
In the same report the check of further connections got no answer on any of three extra connections, and the main connection was closed during it; the log also shows Modbus answers that belonged to an earlier request (transaction id one lower). The owner had also run the tablet app of the system then. A second run with the tablet app stopped gave the same result: the device serves one Modbus TCP client at a time, like the M-TEC module (mtec), and a second connection drops the first.confirmed (one device, two runs)owner's diagnostics report and follow-up comment in #636
A later report of the first owner (0.42.0) was taken while a car charged from PV at a low state of charge. In Solarmax's signs: PV about 3.9 kW, battery about −200 W, grid about −200 W, house (116, read on its own) about 4.3 kW. PV plus battery discharge plus grid import equals the house only with 114 read as + = charging; turned around, the sum is 400 W short, more than the rounding to 100 W explains. The house also contains the charging car (about 3.9 kW in the wallbox's own reading).derived (battery sign, one reading)owner's diagnostics report by e-mail, summarised in #647

Decisions in OpenAmpere

DecisionWhyIssue/PR
Display only: every write method refuses, supports_control is off.EKD switched the storage function off remotely; control also needs "Connectivity+". OpenAmpere never switches it on again.#515, #519
Detected after FoxESS and SAJ, at unit 1, by reading 100–126 with FC04. The device counts as a Solarmax only if firmware (100–999), device state (0–3), nominal power (1–30 kW), state of charge and capacity (at most 100) are all plausible.Detection must not claim another device; SAJ also answers at unit 1, but not with FC04 at 100.#519
Without the counters of "Connectivity+", PV power is the inverter's own DC power (110); the rest of the plant (112 − 110) is shown as a second PV inverter the owner can count, once it was more than 50 W at least once, or with 0 W as soon as the owner counts one (pv.external). With the counters, PV power is the whole plant's (112) and there is no second inverter to count.112 includes other inverters connected to the MAX.STORAGE; without one the app must not offer to count it. What was seen is not stored, so after a restart at night a counted inverter would otherwise be unknown until the sun comes back. The PV counter (150) already includes the connected inverters: counting one on top would count its energy twice.#519
The energy counters (150–159) are used only when they answer and are not all zero, and are no longer asked for after a refusal, or after three reads in a row without an answer if they never answered (counters that answered before are then asked once a minute); there is no load counter, the consumption is their balance.Without "Connectivity+" the device may refuse them, answer zeros or not answer; zeros would look like counters that start at 0, and the live values must never wait for them.#519
Without counters (refused, no answer or all zero) the collector integrates the live powers into lifetime counters of OpenAmpere's own (PV 110, grid 118 and battery 114 split by direction; left Riemann sum, nothing across a gap of more than 2 minutes), kept in the database with each reading so they go on after a restart. Integration starts only once the device is known to have no counters (zeros, refused or never answered), not after one missed read. The energy history, the day values and the counters for Home Assistant come from them. A second inverter the owner counts keeps its own integral (#419). Once real counters answer they are used instead.Before, every day value stayed at 0 on devices without "Connectivity+", which seems to be the usual case for EKD's units. A gap is left empty rather than guessed. Energy from before the update cannot be worked out afterwards: the history starts with it.#636
The connection test of the diagnostics is skipped (SINGLE_CONNECTION). Unlike M-TEC, the setup has no notice to switch other readers off.The device serves one connection: the test only drops OpenAmpere's own connection and tells nothing new. The tablet app apparently does not hold the Modbus connection: OpenAmpere read the device while it ran (derived, one owner). Another Modbus reader (e.g. evcc) would still keep OpenAmpere out; no owner has reported one yet.#636
Device state 3 (error) is reported as a fault; 2 (warning) is not.A warning is no fault the owner must act on.#519
The diagnostics show the powers with Solarmax's own signs (rounded) and whether the "Connectivity+" registers answer, without the serial number and without counter values.So the first owner's report can confirm the signs.#519